Project No. 148
Test Report for the ARID Technologies Vapor Recovery Unit installed in LANTANA, FL
Page 2
2.0 Summary of Results
The emission rate for the vapor control device and vent stack at this gasoline dispensing facility was determined. The results of the test under each condition are summarized in Table 2-1 below.
Table 2-1 Test Results
TERMINAL DESCRIPTION
Retail Gasoline Dispensing
TEST DATE/TEST PERIOD
2/14-15/05
2/15-16/05
2/16-17/05
TEST CONDITIONS
Permeator Off Vent Off
Permeator On
Permeator Off Vent On
GASOLINE LOADED (Gallons)
19,186
19,121
18,908
AVERAGE INLET CONCENTRATION % (C3)
NA
38.52
NA
AVERAGE OUTLET CONCENTRATION % (C3)
39.79
0.72
41.58
AVERAGE HYDROCARBON EMISSION (lbs/1000 gallons)
3.48
0.014
1.20
HYDROCARBON EMISSION RATE (lb/24hr)
66.84
0.27
22.75*
HYDROCARBON REMOVAL EFFICIENCY (calculated using total inlet and outlet masses)
NA
99.27
NA
MTS PERSONNEL IN ATTENDANCE
Harold N. Matus P.E.
*Note: An unquantifiable amount of gasoline vapors were released to atmosphere due to leaky tank fill points and during tank filling operation.