Test Report for the ARID Technologies Vapor Recovery Unit
installed in LANTANA, FL


Page 2

2.0 Summary of Results

The emission rate for the vapor control device and vent stack at this gasoline dispensing facility was determined. The results of the test under each condition are summarized in Table 2-1 below.

Table 2-1 Test Results
TERMINAL DESCRIPTION Retail Gasoline Dispensing
TEST DATE/TEST PERIOD2/14-15/052/15-16/052/16-17/05
TEST CONDITIONSPermeator Off
Vent Off
Permeator OnPermeator Off
Vent On
GASOLINE LOADED (Gallons)19,18619,12118,908
AVERAGE INLET CONCENTRATION % (C3)NA38.52NA
AVERAGE OUTLET CONCENTRATION % (C3)39.790.7241.58
AVERAGE HYDROCARBON EMISSION
(lbs/1000 gallons)
3.480.0141.20
HYDROCARBON EMISSION RATE (lb/24hr)66.840.2722.75*
HYDROCARBON REMOVAL EFFICIENCY
(calculated using total inlet and outlet masses)
NA99.27NA
MTS PERSONNEL IN ATTENDANCEHarold N. Matus P.E.

*Note: An unquantifiable amount of gasoline vapors were released to atmosphere due to leaky tank fill points and during tank filling operation.

Go to page 1 | 3 | 4 | 5 | 6 | 7 | 8
Download report (Word doc)

Field Testing Summary
Table 1: Explanation of Terms
Table 1 - Field Test Data Summary
PERMEATOR On vs Off Graph
Actual independent third-party test results by Matus Technical Services, Inc.
ARID's Evaporative Loss Model
Average V over L Results
Gasoline RVP Samples
Notes Regarding Field Test Leak Results
Field Test Site Photos - Lantana, Florida
 
Home | Back | Top